Stellar Building Performance recently completed blower door testing in Port St. Lucie on two homes at Tesoro Club, working in partnership with Energy Code Compliance Specialists (ECCS). Tesoro Club is an established, gated, master-planned golf community in Port St. Lucie on Florida’s Treasure Coast, and both homes were permitted through the City of Port St. Lucie Building Department. Both passed, at 2.89 and 2.20 ACH50.
If you are building in the city and need envelope leakage testing, you can request blower door testing in Port St. Lucie and we will get you on the schedule.
A 2.89 ACH50 Result at Tesoro Club

The first home moved 1,715 CFM at a 50 Pascal pressure difference across a conditioned volume of 35,559 cubic feet. That works out to 2.89 ACH50.
ACH50 expresses the measured air leakage relative to the volume of the home, allowing the blower door result to account for differences in building size. A large home and a small home can move very different amounts of air through the fan and still land on the same ACH50, which is why the ratio, and not the raw airflow, is the number the energy documentation and the building department work from.

The number this home had to meet was not a universal one. The energy calculation for the project specified 7.0 ACH50, and a different house with different documentation gets a different target. We test against the paperwork the project was actually permitted under.
A 2.20 ACH50 Result at a Second Tesoro Club Home

The second home tested at 1,305 CFM at 50 Pascals across 35,558 cubic feet, which is 2.20 ACH50. The two homes have nearly identical conditioned volumes, about 35,500 cubic feet each, so the difference between them is a clean comparison: 410 CFM of airflow, and about seven tenths of an air change per hour. Two homes that look alike on paper do not always test alike, and that is a big part of why the test gets done on every one.
Working through a community like this one, it helps to have one testing company doing the work on each house, so the builder is not re-explaining the process every time. Get in touch if you would like to talk through a multi-home schedule.
Under 3 ACH50 Means Mechanical Ventilation Has to Be Verified
Both of these homes tested below three air changes per hour. Under the Florida Building Code, Energy Conservation, a dwelling unit that tests under 3 ACH50 has to have whole house mechanical ventilation, and the building department verifies that it is installed. Both reports carry that box checked.
That requirement catches builders out when it shows up at close out instead of during design. Our mechanical ventilation testing is a regular part of what we do on site for exactly that reason, and the tighter new Florida homes get, the more often it applies.
Working With ECCS at Tesoro Club
Both tests at Tesoro Club were completed in partnership with ECCS, and I was onsite for both of them. If you want to see another project we have tested in the city, take a look at our earlier Belterra project in Port St. Lucie.
If your project is in St. Lucie County and you are not sure what testing the permit will call for, the answer is usually in the energy calculation, and we are happy to read it with you. You can also start with a complete blower door testing FAQ.
Testing Across the Treasure Coast and Space Coast
Stellar Building Performance provides blower door testing, duct leakage testing, mechanical ventilation testing, energy code calculations, pre drywall inspections, third party quality assurance and HERS ratings for builders, contractors and owner builders throughout Brevard, Indian River, St. Lucie, Martin and Okeechobee Counties. Need ducts tested on the same house? We also offer duct leakage testing in Port St. Lucie.
To get testing scheduled at Tesoro Club or anywhere else in Port St. Lucie, request services here.