Blower Door Testing in Vero Beach: A 2.87 ACH50 Result at The Strand

New construction home at The Strand where Stellar Building Performance completed blower door testing Vero Beach field work

Stellar Building Performance recently completed blower door testing in Vero Beach for a new construction single family residence at The Strand, a gated community of 47 homesites on Orchid Island between the Indian River Lagoon and the Atlantic. The home was built by GHO Homes. I was onsite performing the test as part of our ongoing work in partnership with Energy Code Compliance Specialists.

The house measured 1,929 CFM50 against a building volume of 40,304 cubic feet, which works out to 2.87 ACH50.

Retrotec blower door panel sealed into the front entry of a Vero Beach home during envelope leakage testing
The blower door takes the place of the front door so the entire house can be held at 50 pascals of negative pressure.

Building on the Vero Beach barrier island and need envelope testing scheduled around your closeout? Request blower door testing in Vero Beach and we will work to your construction calendar.

A 2.87 ACH50 Result at The Strand in Vero Beach

ACH50 expresses the measured air leakage relative to the volume of the home, allowing the blower door result to account for differences in building size. The fan pulls the house to 50 pascals of negative pressure and measures how much airflow it takes to hold it there, reported in cubic feet per minute. Multiply that airflow by 60, divide by the conditioned volume, and you have the number of times the air inside the house turns over in an hour at that test pressure.

On this home the arithmetic runs 1,929 times 60, divided by 40,304, which returns 2.87.

Retrotec gauge reading 1929 CFM at negative 50 pascals during a Vero Beach envelope leakage test
1,929 CFM50 at negative 50 pascals. Against a 40,304 cubic foot building volume that works out to 2.87 ACH50.

The energy documentation for this residence followed the R405 performance path, and the air leakage rate carried on that form was 7.0 ACH50. The measured result landed at well under half of the figure the calculation was built around. Worth saying plainly though: 7 ACH50 is the prescriptive ceiling in Climate Zones 1 and 2 under the 2023 Florida Building Code, Energy Conservation, Eighth Edition. It is not a universal requirement. On a performance or ERI path the target is whatever the energy calculation for that specific house says it is.

If you want to understand how the leakage target on your energy calculation gets set in the first place, we walk through it in our guide to the R405 performance path.

Why 1,929 CFM50 Is Not a Large Number on a House This Size

This is probably my favorite part of this particular Project Update, because the raw airflow number looks alarming right up until you put it next to the volume.

1,929 CFM50 would be a poor result on a modest home. Drop that same airflow into a 15,000 cubic foot house and it comes out around 7.7 ACH50, which does not pass. Spread across 40,304 cubic feet, the identical airflow is 2.87 ACH50.

Open great room and kitchen inside the new Vero Beach home tested for air leakage
40,304 cubic feet of conditioned volume, most of it open to itself.

A larger house has more surface area, more window and door perimeter, more penetrations and more roof to wall transitions. It is expected to move more air in absolute terms. What ACH50 does is ask how leaky the enclosure is relative to what it contains, which is the only fair way to compare an 1,800 square foot home against something like this one.

I bring it up because superintendents sometimes see the CFM reading on the gauge before they see the ACH50 and assume the worst. The number on the screen is not the number that goes on the form.

Questions about where your home is likely to land before test day? That is a conversation we are always glad to have. Reach out about blower door testing anywhere on the Space Coast and Treasure Coast.

What a Result Below 3 ACH50 Triggers in the Florida Energy Code

Testing below 3 ACH50 is not a bonus and it is not a penalty, but it does change one thing. Under Section R402.4.1.2 of the Florida Building Code, Energy Conservation, a dwelling unit with a tested air leakage rate below three air changes per hour must be provided with whole house mechanical ventilation, installed in accordance with Section R403.6.1 of the Energy Code and Section M1507.3 of the Florida Building Code, Residential.

The envelope leakage report carries a check box for exactly this, and the ventilation installation is verified by the building department. At 2.87 ACH50 this home sits on the requiring side of that line.

Blower door fan running in the entry doorway while the home is held at test pressure
The fan holds the house at test pressure while the gauge settles on a stable airflow reading.

The logic behind it is straightforward. A house tight enough to hold onto its conditioned air is also tight enough that it will not reliably exchange stale indoor air on its own, so the code asks for a designed path in rather than an accidental one. Testing is done in accordance with ANSI/RESNET/ICC 380, reported at 0.2 inches of water gauge.

We also perform mechanical ventilation testing, so the ventilation side of a tight house can be verified on the same visit instead of becoming a second trip.

Working With GHO Homes on the Vero Beach Barrier Island

GHO Homes has been building on the Treasure Coast since 1983, when Dan Handler moved the family construction business out of commercial work and into residential. The company has been a subsidiary of Green Brick Partners since 2018 and builds across Indian River and St. Lucie counties.

We have now tested in several of their communities. Over the past couple of months we were at HighPointe in Vero Beach and at Lucaya Pointe, and down in St. Lucie County we worked at Belterra in Tradition. The Strand is a different sort of project from any of those, a small barrier island community of larger homes near the historic Jungle Trail with direct beach access.

Coffered ceiling with exposed beams in a new construction home at The Strand in Vero Beach
Ceiling volume like this is part of why the raw airflow number needs context.

Every one of those visits came through our partnership with Energy Code Compliance Specialists, who coordinate the energy code work across these builds. That arrangement is what lets testing land on the schedule the builder is actually running rather than the other way around.

Red Retrotec fabric panel and fan set into the entry of a new home on Orchid Island in Vero Beach
Setup takes a few minutes. The house does the rest of the talking.

If you build in Indian River County and want energy code testing that keeps pace with your production schedule, here is how we work with builders and developers.

A First Training Day on the Blower Door at The Strand

There was a first on this job that has nothing to do with the number. I started training my wife on blower door testing.

Stellar is a family company, and as it keeps growing she is going to be taking on testing work alongside me. This was day one of that.

There is more to this than switching on a fan. The frame and panel have to seal properly in the opening, the gauge and pressure tubing have to be set up right, and the house has to be configured to the standard before a single reading counts for anything. Then somebody has to know what the number means once it lands, and what to do when it does not land where it should. That is the part that takes time, and it is learned on real houses rather than in a classroom, which is why it started on a job site.

More of that ahead. For now it is worth writing down that it started here, at The Strand.

Growing the bench is how we keep coverage tight across five counties without stretching the schedule. A little more about who we are and how we work is on the about page.

Blower Door Testing Across Vero Beach and Indian River County

Orchid Island projects sit in a particular environment. Salt air, high humidity, a lot of glass facing the water and homes designed to open up to the outside. None of that changes how a blower door test is run, but it does mean the envelope details are worth looking at closely rather than filing the report and forgetting it.

Foyer of a GHO Homes residence at The Strand during envelope leakage testing in Vero Beach
Interior doors stay open during the test so the whole conditioned volume is pulled down together.

We cover Vero Beach and the rest of Indian River County regularly, including Sebastian, Fellsmere, Orchid and Indian River Shores, and we are on the island often enough that adding a home to an existing trip is usually straightforward.

Stellar Building Performance provides blower door testing, duct leakage testing, infrared thermography, duct smoke testing, mechanical ventilation testing, energy and load calculations, HERS Ratings and third party quality assurance across Brevard, Indian River, St. Lucie, Martin and Okeechobee counties.

Ready to get a test on the calendar in Vero Beach? Request services and tell us what you have coming up.

Comments are closed

ExcellentGoogle star 1Google star 2Google star 3Google star 4Google star 55.04 reviews
5.0Google star 1Google star 2Google star 3Google star 4Google star 5
Excellent4 reviews
Posted on Google Google
Pher Logsdon profile picture
Pher Logsdon
72 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Mario with Stellar Building Performance came in clutch today. I was informed by the plans review department of SLC that I needed to complete a blower door test on my nearly finished new construction home. I got in touch with Mario, and he could not have been more professional. He answered all my questions and informed me he would be out the same day. He showed up on time and completed his test, explaining the process. When he finished, he issued my certificate on the spot. This was a great experience, and I would definitely recommend his services.
Posted on Google Google
Ky Sims profile picture
Ky Sims
91 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Mario was prompt, knowledgeable, friendly & thorough. Pleasure doing business with him.
Posted on Google Google
Shana Storti-Massaux profile picture
Shana Storti-Massaux
91 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
I cannot recommend Stellar Building Performance and the owner, Mario, enough! We purchased our 1993 home in Viera in mid-February, after having a thorough home inspection completed. When the first truly hot days of summer arrived, however, we realized our air conditioning system was struggling to keep up. An HVAC company we had used in the past told us it was not the system itself and suggested expensive work in the attic. But, before spending thousands of dollars, we wanted an unbiased opinion from someone who wasn’t trying to sell us equipment or additional services. That’s exactly what we found with Mario. He performed an incredibly thorough home energy audit that included a heat load and air leakage investigation, blower door testing with detailed notes and photos, duct leakage testing, infrared imaging, room-by-room pressure measurements, and comprehensive insulation inspections of both the walls and attic. More importantly, he took the time to explain verbally, and with a written report, what he was finding, why it mattered, and what improvements would provide the greatest benefit for our home. The report and recommendations were detailed, educational, and gave us the confidence to make informed decisions instead of simply accepting costly recommendations from contractors. What impressed me most was Mario’s integrity. He had nothing to sell us other than his expertise, which made his recommendations feel completely trustworthy. Even after the audit was finished, he continued checking in to see how things were going and what improvements we had made. That level of follow-up and genuine concern for his clients is rare today. If you’re experiencing high energy bills, uneven temperatures, an overworked HVAC system, or simply want to understand how your home is performing before investing in repairs, Stellar Building Performance is absolutely worth the very reasonable cost. Mario’s knowledge, professionalism, and commitment to helping homeowners make informed decisions exceeded every expectation.
Posted on Google Google
Airwayz Air duct profile picture
Airwayz Air duct
212 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
If I could give 10 stars, I absolutely would. We had the pleasure of working with Mario from Stellar Building Performances, and the name of his company truly says it all, stellar from start to finish. Mario went completely above and beyond in every aspect. His attention to detail is on another level, and his communication throughout the entire process was clear, consistent, and professional. What really stood out was his willingness to go the extra mile, he didn’t just do the job, he made sure everything was done right. He even took the time to consult with building departments across multiple counties to ensure accuracy and compliance, which is something you rarely see. That level of dedication and care is hard to find. It’s rare to come across someone who is not only knowledgeable, but genuinely committed to helping and doing things the correct way. Mario is exactly that. We highly, highly recommend Stellar Building Performance to anyone looking for quality, professionalism, and someone who truly cares about their work. Lissette F Operation Manager at Airwayz Airduct & Insulation Services LLC
Verified by Trustindex
Trustindex verified badge is the Universal Symbol of Trust. Only the greatest companies can get the verified badge who has a review score above 4.5, based on customer reviews over the past 12 months. Read more